SMART Current Driver/Repeater KFD0-SCS-Ex1.55

KFD0-SCS-Ex1.55
  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current input/output 4 mA ... 20 mA
  • HART-IP or transmitter power supply
  • Low voltage drop
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Technische gegevens  KFD0-SCS-Ex1.55

General specifications
Signal typeAnalog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Rated voltage< 30 V DC , loop powered
Power dissipation0.2 W
Control circuit
Connectionterminals 8-, 9+
Voltagemax. 30 V DC
Current4 ... 20 mA (quiescent current < 0.5 mA)
Power dissipation150 mW at 20 mA and Uin < 24 V
Field circuit
Connectionterminals 1+, 2 / 3-
Voltage≥ 16 V for supply voltage > 21 V
Current4 ... 20 mA (linear transmission 1 ... 22 mA)
Load≤ 800 Ω (at 20 mA)
Transfer characteristics
Voltage dropsee note
Deviation
After calibration≤ ± 80 µA linearity, load and voltage dependence at 20 °C (68 °F)
Influence of ambient temperature< 0.5 µA/K
Dampingapprox. 3 dB
Rise time≤ 20 µs at 0 Ω, ≤ 600 µs with 800 Ω load
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 120 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2
Height112 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 02 ATEX 2064
MarkingEx-Hexagon II (2)G [EEx ib] IIC
Voltage23.1 V DC
Current28 mA
Power0.647 W
Supply
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
CertificatePF 11 CERT 0902 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approvaldevice with FM approval on request
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD0-SCS-Ex1.55

Datasheet: KFD0-SCS-Ex1.55

DatasheetBestandstypeBestandsgrootte
Datasheet KFD0-SCS-Ex1.55PDF1109 KB
Fiche de données KFD0-SCS-Ex1.55PDF1092 KB
Datenblatt KFD0-SCS-Ex1.55PDF1089 KB
Datasheet KFD0-SCS-Ex1.55PDF1145 KB
Hoja de datos KFD0-SCS-Ex1.55PDF1118 KB

Documents: KFD0-SCS-Ex1.55

ManualsBestandstypeBestandsgrootte
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF135 KB
Návod k poużitíPDF131 KB
Instruktions manualPDF129 KB
Instruction manualPDF135 KB
KasutusjuhendPDF126 KB
KäyttöohjePDF125 KB
Manuel d'instructionsPDF130 KB
BetriebsanleitungPDF135 KB
Οδηγίες χρήσηςPDF138 KB
HandleidingPDF129 KB
Instruction manual / BetriebsanleitungPDF129 KB
Használati útmutatóPDF131 KB
Manuale di istruzioniPDF129 KB
Lietošanas pamācībaPDF129 KB
Instrukciju vadovasPDF130 KB
Instrukcja obsługiPDF131 KB
Manual de instruçõesPDF130 KB
Manual de utilizarePDF130 KB
Návod na poużitiePDF130 KB
Navodila za uporaboPDF128 KB
Manual de instruccionesPDF130 KB
ManualPDF127 KB
Application reports
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB

CAD+CAE: KFD0-SCS-Ex1.55

CADBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DSTP3048 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ942 KB

Approvals+Certificates: KFD0-SCS-Ex1.55

CertificatesBestandstypeBestandsgrootte
Europe PTB ATEX Category (2) GPDF6215 KB
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PDF179 KB
South Africa MASCPDF209 KB
exida Functional Safety AssessmentPDF284 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF82 KB

Aanverwante producten: KFD0-SCS-Ex1.55

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa