Resistance Repeater KCD2-RR2-Ex1

KCD2-RR2-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Housing width 12.5 mm
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Technische gegevens  KCD2-RR2-Ex1

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Rated current< 28 mA
Power consumption0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4
Line fault detectionyes , at Pt100
Lead resistance≤ 10 % of resistance value
Transmission range0 ... 10 mA
Available voltage7 V
Line fault detection< 30 nA
Output
Connection sidecontrol side
Connectionterminals 5-, 7-, 6+, 8+
Current0 ... 10 mA
Available voltage0 ... 4.2 V
Fault signalfield voltage < 150 mV or > 4 V, depending on lead disconnected
Reverse polarity protectionfor I < 10 mA or U < 20 V
Transfer characteristics
Accuracy0.1 %
DeviationIm ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable).
Influence of ambient temperatureIm ≥ 1 mA, Rm ≥ 100 Ω: 0.01 %/K in the range -20 ... +70 °C (-4 ... 158 °F)
Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm
Settling time≤ 5 ms
Rise time/fall time≤ 2 ms (10 ... 90%)
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
EN IEC 61326-3-2:2018
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Height119 mm
Width12.5 mm
Depth114 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 10 ATEX 0061X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage9.5 V
Current39.22 mA
Power93 mW
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 10 ATEX 0062X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
FM approval
FM certificateFM 19 CA 0039 X , FM 19 US 0067 X
Control drawing116-0457 (cFMus)
UL approvalE106378
Control drawing116-0332 (cULus)
IECEx approval
IECEx certificateIECEx BAS 10.0024X
IECEx BAS 10.0025X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KCD2-RR2-Ex1

Datasheet: KCD2-RR2-Ex1

DatasheetBestandstypeBestandsgrootte
Datasheet KCD2-RR2-Ex1PDF1182 KB
Fiche de données KCD2-RR2-Ex1PDF1217 KB
Datenblatt KCD2-RR2-Ex1PDF1203 KB
Datasheet KCD2-RR2-Ex1PDF1333 KB
Hoja de datos KCD2-RR2-Ex1PDF1221 KB

Documents: KCD2-RR2-Ex1

ManualsBestandstypeBestandsgrootte
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF173 KB
Instruction manual / BetriebsanleitungPDF328 KB
Návod k poużitíPDF168 KB
Instruktions manualPDF166 KB
Instruction manualPDF172 KB
KasutusjuhendPDF163 KB
KäyttöohjePDF163 KB
Manuel d'instructionsPDF169 KB
BetriebsanleitungPDF173 KB
Οδηγίες χρήσηςPDF176 KB
HandleidingPDF167 KB
Instruction manual / BetriebsanleitungPDF166 KB
Használati útmutatóPDF169 KB
Manuale di istruzioniPDF167 KB
Lietošanas pamācībaPDF166 KB
Instrukciju vadovasPDF167 KB
Instrukcja obsługiPDF169 KB
Manual de instruçõesPDF168 KB
Manual de utilizarePDF167 KB
Návod na poużitiePDF168 KB
Navodila za uporaboPDF165 KB
Manual de instruccionesPDF168 KB
ManualPDF164 KB
Application reports
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Functional Safety ManualPDF1412 KB
Handbuch funktionale SicherheitPDF1419 KB

CAD+CAE: KCD2-RR2-Ex1

CADBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DSTP3085 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ1686 KB

Aanverwante producten: KCD2-RR2-Ex1

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
2-pin, Fully insulated, For connectors with 5.0 mm or 5.08 mm pitchpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces greenpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.