SMART Current Driver KFD2-SCD2-Ex2.LK

KFD2-SCD2-Ex2.LK
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Current output up to 650 Ω load
  • HART-IP and valve positioner
  • Line fault detection (LFD)
  • Accuracy 0.1 %
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Technische gegevens  KFD2-SCD2-Ex2.LK

General specifications
Signal typeAnalog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 45 mA at 24 V
Power dissipation≤ 1 W at 20 mA and 500 Ω load
Power consumption≤ 1 W
Input
Connection sidecontrol side
Connectionterminals 7-, 8+, (9+); 10-, 11+, (12+)
Input signal4 ... 20 mA , limited to approx. 30 mA
Input voltageopen loop voltage of the control system ≤ 30 V
Voltage dropapprox. 6 V at 20 mA
Input resistancefield wiring open circuit : > 100 kΩ
field wiring < 50 Ω : > 100 kΩ when using terminals 1, 2 and 4, 5
Output
Connection sidefield side
Connectionterminals 1+, 2-; 4+, 5-
terminals 3+, 2-; 6+, 5- (no short circuit detection)
Voltage≥ 13 V at 20 mA
Current4 ... 20 mA
Load100 ... 650 Ω , for terminals 1, 2; 4, 5
0 ... 550 Ω , for Terminals 2, 3; 5, 6
Ripple20 mV rms
Line fault detectionbreakage, load > 100 kΩ, short-circuit, load < 50 Ω
Fault indication output
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Deviationat 20 °C (68 °F), 4 ... 20 mA
< 0.1 % of full scale, incl. non-linearity and hysteresis
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % ≤ 10 ms
Galvanic isolation
Input/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/inputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLEDs
Labelingspace for adhesive label at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
EN 61326-3-2:2018
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 135 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2
Height124 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBAS 00 ATEX 7240 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia, Ex iaD
Voltage25.2 V
Current93 mA
Power585.3 mW
Internal capacitance1.05 nF
Internal inductance0
Supply
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.)
CertificateFIDI 22 ATEX 0002 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018
International approvals
UL approvalE106378
Control drawing116-0345 (cULus)
IECEx approval
IECEx certificateIECEx BAS 04.0014X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SCD2-Ex2.LK

Datasheet: KFD2-SCD2-Ex2.LK

DatasheetBestandstypeBestandsgrootte
Datasheet KFD2-SCD2-Ex2.LKPDF1164 KB
Fiche de données KFD2-SCD2-Ex2.LKPDF1168 KB
Datenblatt KFD2-SCD2-Ex2.LKPDF1165 KB
Datasheet KFD2-SCD2-Ex2.LKPDF1171 KB
Hoja de datos KFD2-SCD2-Ex2.LKPDF1166 KB

Documents: KFD2-SCD2-Ex2.LK

ManualsBestandstypeBestandsgrootte
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF173 KB
Instruction manual / BetriebsanleitungPDF334 KB
Návod k poużitíPDF168 KB
Instruktions manualPDF167 KB
Instruction manualPDF172 KB
KasutusjuhendPDF163 KB
KäyttöohjePDF162 KB
Manuel d'instructionsPDF169 KB
BetriebsanleitungPDF173 KB
Οδηγίες χρήσηςPDF176 KB
HandleidingPDF167 KB
Instruction manual / BetriebsanleitungPDF166 KB
Használati útmutatóPDF169 KB
Manuale di istruzioniPDF167 KB
Lietošanas pamācībaPDF166 KB
Instrukciju vadovasPDF168 KB
Instrukcja obsługiPDF169 KB
Manual de instruçõesPDF168 KB
Manual de utilizarePDF168 KB
Návod na poużitiePDF168 KB
Navodila za uporaboPDF165 KB
Manual de instruccionesPDF169 KB
ManualPDF164 KB
Application reports
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Functional Safety ManualPDF1969 KB
Handbuch funktionale SicherheitPDF1984 KB

CAD+CAE: KFD2-SCD2-Ex2.LK

CADBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DSTP3048 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ1641 KB

Aanverwante producten: KFD2-SCD2-Ex2.LK

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.