PROFIBUS Power Hub, Gateway Module HD2-GTR-4PA

HD2-GTR-4PA
  • PROFIBUS DP V1 / For 4 segments PA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • Optional redundant configuration
  • Installation in Zone 2/Class I, Div. 2
  • Up to 12 Mbit/s, auto adapting
  • For redundant and non-redundant masters
  • Supports Flying Redundancy (FR)
  • Cyclic/acyclic data exchange

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Technische gegevens  HD2-GTR-4PA

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC
Rated current160 ... 90 mA
Power dissipation3 W
Fieldbus connection
PROFIBUS DP
Connection9-pin Sub-D socket
ProtocolPROFIBUS DP V1
Indicators/operating means
LED Seg 1...4red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error
LED PWRgreen: Power on
LED DP/ERRred 2 Hz flashing: DP error ; red: Hardware error
LED Red.yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available
Galvanic isolation
CH/PROFIBUS DPfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
PROFIBUS DP/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
CH/CHfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Low voltage
Directive 73/23/EECEN 50178 (identical to EN 62103)
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Degree of protectionIP20
Mass250 g
Dimensions
Height106 mm
Width40 mm
Depth128 mm
Mountingmotherboard mounting , mounting in any orientation
Data for application in connection with hazardous areas
CertificateTÜV 04 ATEX 2500 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex ec IIC T4
IECEx approval
IECEx certificateIECEx TUN 13.0038X
IECEx markingEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001600
ETIM 8.0EC001600
ETIM 7.0EC001600
ETIM 6.0EC001600
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: HD2-GTR-4PA

Datasheet: HD2-GTR-4PA

DatasheetBestandstypeBestandsgrootte
Datasheet HD2-GTR-4PAPDF907 KB
Datenblatt HD2-GTR-4PAPDF971 KB

Documents: HD2-GTR-4PA

ManualsBestandstypeBestandsgrootte
Manual for use with HD2-FB*, MB-FB*.GEN, MBHD-FB*.GEN, MBHD-FB-D-4R.GEN, MB-FB-GT, MB-FB-GTRPDF2401 KB
Manual für use with HCD2-FB*, MBHC-FB-4.HSC*, MBHC-FB-4R.HSC*, MB-FB-GTR1, MBHC-FB-4.GTPDF3939 KB
Handbuch für Einsatz mit HD2-FB*, MB-FB*.GEN, MBHD-FB*.GEN, MBHD-FB-D-4R.GEN, MB-FB-GT, MB-FB-GTRPDF3036 KB
Instruction manuals
ИнструкцииPDF164 KB
Instruction manual / BetriebsanleitungPDF304 KB
Návod k poużitíPDF159 KB
Instruktions manualPDF159 KB
Instruction manualPDF168 KB
KasutusjuhendPDF155 KB
KäyttöohjePDF155 KB
Manuel d'instructionsPDF160 KB
BetriebsanleitungPDF169 KB
Οδηγίες χρήσηςPDF166 KB
HandleidingPDF159 KB
Instruction manual / BetriebsanleitungPDF158 KB
Használati útmutatóPDF160 KB
Manuale di istruzioniPDF158 KB
Lietošanas pamācībaPDF157 KB
Instrukciju vadovasPDF159 KB
Instrukcja obsługiPDF161 KB
Manual de instruçõesPDF159 KB
Manual de utilizarePDF159 KB
Návod na poużitiePDF159 KB
Navodila za uporaboPDF156 KB
Manual de instruccionesPDF159 KB
ManualPDF157 KB
Application reports
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingPDF470 KB
Application Report - Fieldbus Power Supply Compatible with Process Industry ApplicationsPDF229 KB
Applikationsbericht - Digitale Kommunikation in der Produktion von GrobblechenPDF473 KB
Applikationsbericht - Kompatible Feldbus-Stromversorgung für die ProzessindustriePDF231 KB
Applikationsbericht - Steuerung und Überwachung der Kälteanlagen im Deutschen Elektronen-SynchrotronPDF643 KB
Documents
Design Guideline FieldConnex - Exchange and replacement for Segment Coupler 1, 2, and 3PDF902 KB
Design-Richtlinie FieldConnex - Austausch und Ersatz für Segmentkoppler 1, 2 und 3PDF903 KB

Approvals+Certificates: HD2-GTR-4PA

CertificatesBestandstypeBestandsgrootte
Canada FMPDF356 KB
China SITIIAS CCCPDF1330 KB
DNV MarinePDF100 KB
Europe TUV Nord ATEX Category 3 GPDF1498 KB
India PESO (India) CCOEPDF101 KB
USA FMPDF213 KB
Worldwide TUV Nord Ex nA nC IECEx nALINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF1039 KB

Software: HD2-GTR-4PA

Device DriverBestandstypeBestandsgrootte
GSD / GSDZIP6 KB
Device type managers (DTM)
DTM Collection FieldConnex / DTM Collection FieldConnexZIP35363 KB
Software Tools
GSD converter for transparent gateways / GSD-Konverter für transparente GatewaysZIP793 KB

Aanverwante producten: HD2-GTR-4PA

Matching System Components
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectable, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Device coupler location [3]: Zone 1 - high-power trunkpa
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnostics, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Accessories
User interface for PROFIBUS components, Simple access to measurements, diagnostic and configuration data, Supports any FDT/DTM hostpa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa

Ethernet-APL zorgt voor een ononderbroken gegevensoverdracht over alle hiërarchische niveaus. Leer meer over deze baanbrekende technologie...

RSS-Meldingen voor PANOS-Updates

Ontvang een automatische melding wanneer een nieuwe software-update voor PANOS, het besturingssysteem voor Ethernet-APL-schakelaars, beschikbaar is: Zodra een update wordt vrijgegeven, ontvangt u via onze RSS-feed onmiddellijk een e-mailbericht in uw inbox.

Van beslissing over planning, installatie en indienstname tot gebruik en onderhoud: Ontdek hoe u het beste uit uw veldbusinfrastructuur kunt halen…